GTC-ETCH

8 Channel EtherCAT Module

  • Digital calibration technology for input measurement.

  • Supports various thermocouples and RTDs.

  • Auto tuning (AT) control.

  • DIN rail mounting.

  • User-friendly operation interface.

  • Can be easily adapted to your panels with a 24 VDC power supply.

  • Enhanced anti-interference capability developed for operation in adverse industrial environments.

  • Supply: 24 VDC (-15%, +10% tolerance)

  • Power Consumption: ≤ 5W

  • Supported Sensor Types:

    • Thermocouple: K, S, R, E, J, T, B, N, WRe3-WRe25, WRe5-WRe26

    • RTD: Cu50, Pt100

    • DC Voltage: 0~5V, 1~5V, 0~1V, 0~100mV, 0~20mV, 0~500mV, etc.

    • DC Current: 4~20mA (with 250 Ohm shunt resistor)

  • Reading Range (Temperature):

    • K (-50~1300°C), S and R (-50~1700°C), T (-200~ +350°C), E (0~800°C), J (0~1000°C), B (200~1800°C), N (0~1300°C)

    • Cu50 (-50~ +150°C), Pt100 (-200~ +600°C)

  • Measurement Accuracy: 0.25%FS ± 1 measured unit

  • Control Period (Cycle Time): 0.24~300.0 seconds selectable, and this value must be in integer multiples of 0.5 seconds.

  • Control Mode: On-Off control mode (deadband adjustable). Fuzzy logic PID control, auto-tuning with AI-PID (advanced artificial intelligence algorithm).

  • Output Specifications: SSR Output: 12VDC/30mA (for driving SSR)

  • Sampling Period: Can sample 8 times per second. Response time can be set to 0.5 seconds (by setting the digital filter parameter FILt=0).

  • Function (Alarm): Upper limit, lower limit, deviation upper limit, deviation lower limit.

  • Electromagnetic Compatibility (EMC): ± 4KV/5KHz according to IEC61000-4-4; 4KV according to IEC61000-4-5.

  • Isolation Withstand Voltage: ≥ 600V between terminals.

  • Operating Conditions: Temperature -10~60°C, Humidity ≤ 90%RH

  • Communication: Modbus RTU (RS485) 9600, 8, None, 1