GTC12S-D
Universal Input, SSR+Relay Output (Heating/Cooling), Dual PID Control Device
Digital calibration technology for input measurement.
Supports various thermocouples, RTC (RTD is the likely correct term here), DC voltage, DC current.
Auto tuning (AT) control.
DIN rail mounting.
User-friendly operation interface.
Can be easily adapted to your panels with a 24 VDC power supply.
Enhanced anti-interference capability developed for operation in adverse industrial environments.
Supply: 24 VDC (-15%, +10% tolerance)
Power Consumption: ≤ 5W
Supported Sensor Types:
Analog: 4-20mA
Thermocouple: J, K, S, R, E, T, B, N, WRe3-WRe25, WRe5-WRe26
RTD: Cu50, Pt100
DC Voltage: 0~5V, 1~5V, 0~1V, 0~100mV, 0~20mV, 0~500mV, etc.
DC Current: 4~20mA (with external 250 Ohm shunt resistor)
Reading Range (Temperature):
J (0~1000°C), K (-50~1300°C), S and R (-50~1700°C), T (-200~ +350°C), E (0~800°C), B (200~1800°C), N (0~1300°C)
Cu50 (-50~ +150°C), Pt100 (-200~ +600°C)
Measurement Accuracy: 0.25%FS ± 1 measured unit
Control Mode: On-Off control mode (deadband adjustable). Fuzzy logic PID control, auto-tuning with AI-PID (advanced artificial intelligence algorithm).
Output Specifications (Heating/Cooling):
1st Control Output (Heating): SSR (12VDC)
2nd Control Output (Cooling): Relay (230VAC)
Alarm Function: Upper limit, lower limit, deviation upper limit, and deviation lower limit.
Electromagnetic Compatibility (EMC): ± 4KV/5KHz according to IEC61000-4-4; 4KV according to IEC61000-4-5.
Isolation Withstand Voltage: ≥ 600V between terminals.
Operating Conditions: Temperature -10~60°C, Humidity ≤ 90%RH
Communication: Modbus RTU: RS485 9600, 8, None, 1
Mounting Information: DIN Rail Mounting